IP40 rod type temperature cut-out thermostat - Adjustable range from 10 to 90 °C with temperature limiter at 100 °C

Product N° : 9030.41
Vulcanic IP40 rod type thermostat 10 to 90 °C and temperature limiter 100 °C 903041 View1
search
  • Vulcanic IP40 rod type thermostat 10 to 90 °C and temperature limiter 100 °C 903041 View1
  • Vulcanic IP40 rod type thermostat 10 to 90 °C and temperature limiter 100 °C 903041 View2
  • IP40 rod type thermostat 10 to 90 °C and temperature limiter 100 °C 903041 Vulcanic Draw
  • Vulcanic IP40 rod type thermostat 10 to 90 °C and temperature limiter 100 °C 903041 View3
  • Vulcanic IP40 rod type thermostat 10 to 90 °C and temperature limiter 100 °C 903041 View4

Rod type temperature cut-out thermostat with temperature limiter, in an IP40 junction box, designed to measure the temperature of a gas or a liquid in a tank or in a pipe. Operating on the principle of fluid expansion, the sensitive part of the thermostat is inserted in a copper thermowell equipped with a 1/2'' cylindrical gas threaded connection to allow the thermostat to be mounted and ensure sealing with the fluid being measured. Adjustable control range from +10 to 90 °C with automatic reset and fixed cut-off temperature preset at 100 °C with manual reset for the limiter. Switching capacity: 15 A / 230 V or 10 A / 400 V.

Last items in stock 1 items

Function :
Regulation and limiter
Regulation temperature range :
Adjustable from +10 to +90 °C
Control reset mode :
Automatic
Number of control contacts :
1 changeover contact
Switching differential of the control system :
6 °C
Limiter setting temperature :
100 °C Permanent
Limiter reset mode :
Manual
Number of limiter contacts :
1 Normally open contact
Cut-off tolerance of the limiter :
+0 / - 6 °C
Switching capacity :
15A, 230V / 10A, 400V
Length of thermowell L (mm) :
110
Thermowell diameter (mm) :
16
Thermowell material :
Copper
Connection thread :
1/2'' Conical gas
Protection class of the junction box :
IP40
Position of the control knob :
Outside of junction box
Position of the limiter reset button :
Outside of junction box
Electrical connection :
Stirrup terminals
Weight (kg) :
0.33