Self-adapting, single-loop PID temperature controller with 3 outputs. K thermocouple input, temperature range preset to 0/+1200 °C. Control output 1: 2A/240 VAC changeover relay, outputs 2 and 3: relay for alarm control. IP66 front panel, size 48 x 48 mm, equipped with a 4-key keypad for setting the device and a double 4-digit display for reading the setpoint and the measurement. Power supply 100 to 240 V 1P. The device can be mounted on the front of a cabinet or on a Din rail. Possibility to program a temperature ramp up to the setpoint. Option A is not equipped.

Available, 5 items

Front dimensions (mm) :
48 x 48
Input signal :
K Thermocouple
Preset temperature range (°C) :
0 / +1200
Number of control loops :
1
Regulation mode :
PID
Control output on Slot 1 :
Switch
Relay on control output :
1 Changeover contact 2A max / 240 V AC
Adjustment mode :
Self-adapting or manual
Exit on Slot n° 2 :
Alarm
Exit on Slot n° 3 :
Alarm
Alarm relay :
1 Changeover contact 2A max / 240 V AC
Retransmission of measurement or setpoint on Slot A :
Not assembled
Regulator supply voltage (V) :
100 / 240
Number of setpoints :
1
1 Configurable setpoint ramp :
Oui
Accuracy :
+/-0.1% of input scale +/-1 digit
Operator interface :
4-button keypad
Display of values :
Two 4-digit displays for setpoint and measurement
Display colour :
Measurement: Red - Setpoint: Green
Cut-out for mounting (mm) :
45 x 45 (0/+0,5)
Regulator Depth D (mm) :
110
Front panel protection :
IP66
Controller assembly :
Front or Din rail mounted
Operating temperature :
0 to 55 °C (storage from -20 to 80 °C)
Hygrometry :
20% to 95% HR without condensation
Weight (kg) :
0.18