Vulcatherm Hot/Refrigerated - Glycolated Water 140 °C max - Heating power 6kW / 400V 3P - With water cooled refrigerating unit

Product N° : 10826.06
Temperature control units Vulcatherm Hot/Refrigerated Water 10826 Vulcanic Vue1
search
  • Temperature control units Vulcatherm Hot/Refrigerated Water 10826 Vulcanic Vue1
  • Temperature control units Vulcatherm Hot/Refrigerated Water 10826 Vulcanic Draw
  • Opertaing curve of Vulcatherm Hot/Cold Vulcanic Draw

Vulcatherm temperature control unit Hot/Refrigerated for heating, cooling and regulating a closed loop of glycol water from -20°C to 140°C max intended for crystalizers, chemical reactors, climatic chambers, test benches, etc. Power heat 6 kW / 400 V 3P + E. Cooling by integrated refrigerating unit and exchanger/condenser supplied by the customer's industrial water network. Pressurization of the circuit at 3 bar.g with electric expansion by solenoid valve. max admissible pressure of 14 bar.g in the circuit.

Can be made , Under 70 days

The Vulcatherm temperature control unit consists of:

- 1 Electrical heater with temperature sensors

- 2 Pumps

- 1 Membrane expansion tank

- 1 Filling and expansion tank

- 1 Evaporator exchanger

- 1 Condenser water cooled

- 1 Refrigerating compressor

- 1 Electrical cabinet with integrated Central Management System

- Sensors for control and safety

in a painted frame equipped with castors

Vulcatherm model :
Hot/Refrigerated
Heat transfer medium :
Water + glycol
Type of heat transfer medium expansion :
Autonomous pressurisation to 3 bar.g with electric expansion (via solenoid)
Heating power (kW) :
6
Tolerance on heating power :
+5/-10%
Supply voltage :
400 V 3P + E
Maximum current absorbed at 400 V 3P (A) :
19
Maximum temperature of the heat transfer medium (°C) :
140
Cooling power :
6KWFluide0Eau25
Minimum temperature of the heat transfer medium (°C) :
-20
Cooling device :
Refrigeration unit with water cooling (customer network)
Maximum pressure allowed in the current (bar.g) :
14
Nominal flow of the heat transfer medium :
0.9 m3/h at delta P of 4 bar
Expansion volume (l) :
9.4
Medium inlet and outlet connections :
3/4'' male gas thread
Système de gestion centralisé (automate)
Integrated central management (controller)
Body material :
Painted frame equipped with castor
Vulcatherm dimensions (mm) :
L: 800 x H: 1200 x D:800
  • User manual